Question 1
A project requires both Class A external roof-fire performance and a two-hour fire-resistance rating for the roof-ceiling assembly. The submitted UL 790 Class A listing matches the proposed roof covering, insulation, and deck, but no other fire-test documentation is provided. What evidence is still needed to establish the separate two-hour requirement?
Show answer & explanation
Correct answer: C - A two-hour UL 263/ASTM E119 fire-resistance listing matching the complete proposed roof-ceiling construction.